Wuhan Unique Mechanical and Electrical Equipment Co.,Ltd.
|
Payment Terms: | T/T,L/C |
Place of Origin: | Hubei, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
HUAWEI R48100G1 48V 6000W Rectifier Module
R48100G1 Short Brief: The R48100G1 is a digital control 3-phase rectifier with the maximum output power being 6000W. It converts 260~530VAC input voltage to 53.5VDC output voltage. The output voltage can be adjusted by the host. It performs comprehensive protection functions, supports soft start, and produces low noise. With the latest power monitoring technology, states of the rectifier and load are monitored in real time. Multiple rectifiers can be paralleled.
48V 6000W Rectifier Features:
1) Input voltage range: 260~530VAC
2) Operating temperature range: -40 ºC to +75 ºC (output derating above 45ºC)
3) Total harmonic distortion (THD): ≤ 5%
4) Digital control mode
5) Hot swap
6) Supports intelligent electric meter
7) Supports CAN communication
8) Supports LED display
9) Supports voltage and current adjustment
10) Passes the TUV,CE,UL certifications and gets the CB certificate
HUAWEI R48100G1 120A Rectifier Specification
R48100G1 Weight: 6kg
Dimensions: 43 x 238 x 378mm
R48100G1
HUAWEI R48100G1 48V 6000W rectifier module
Notes
1. We will ship the item in 3-5 work days after the payment arrive.
2. We will usually ship the item to Worldwide by FedEx/ UPS/DHL.
3. Buyer's responsibility to pay customs fees, duties, import taxes, shipping charge
And related charges.
4. We accept the payment through T/T, Paypal, and Western Union.
5. The pictures show you one of the items in stock. But the exact one may be sold before your bidding. So it may not the exact one which you will receive.
Specifications
Product Type | R48100G1 | |
Basic Specifications | Dimension | 238 mm(W) × 378 mm(D) × 43 mm(H) |
Weight | ≤ 6.0 kg | |
Cooling | Forced air cooling (Built-in fan) | |
Input Feature | Input Voltage | 260 to 530 Vac |
AC Input Mode | 380 Vac three-phase three-line | |
Frequency | 45 to 66 Hz, rated: 50/60 Hz | |
Maximum Input Current | ≤ 13 A | |
Power Factor | ≥ 0.99 (Vin: 360 Vac, 380 Vac, 415 Vac, three-phase balance) | |
THD | ≤ 5% (Vin: 308 to 480 Vac) | |
Output Feature | Efficiency | > 96% Max |
Output Voltage | 43.2 to 58 Vdc, rated voltage: 53.5 Vdc | |
Output Power | 6000W (304 to 530 Vac ) | |
Ripple and Noise | < 200 mV pk-pk, 20 M bandwidth, < 2 mV rms psophometric | |
Hold-up Time | > 10 mS at 6000 W , output voltage > 42 V | |
Output Regulated Voltage Precision | ≤ 0.6% Vo from no load to full load | |
Current Share | ±5% output rated current from 10% to 100% load | |
Environmental Specifications | Operating Temperature | -33 ℃ to +75 ℃ (non-derating below 45 ℃), ETS EN 300-019 |
Storage Temperature | -40 ℃ to +75 ℃; ETS EN 300-019 | |
Relative Humidity | 5% to 95% (non-condensing), ETS EN 300-019 | |
Altitude Range | ≤ 4000 m (If the altitude is within the range of 2000 m to 4000 m, the maximum operating temperature decreases by 1℃ as the altitude increases by 200 m) | |
Protection | Input Overvoltage Protection | Protection point: 530 to 550 Vac |
Input Under-voltage Protection | Protection point: < 260 Vac | |
Output Over-voltage Protection | 58.5 to 60.5 Vdc (can be set by monitoring unit) | |
Output Short Circuit Protection | A long term short circuit is allowed. After the fault is rectified, the rectifier will restore automatically | |
Over-temperature Protection | Protection point: > 75 ℃ | |
Reliability | MTBF | ≥ 500,000 hours (Telcordia SR-332 issue2 Method 1 at 25 ℃) |
Audible Noises | Specification | ≤ 45dB (25 ℃, full load); sound presure@1m distance, ISO3744 |
Safety/EMC/ Lightening Protection | Safety Certification | Passed TUV, CE, UL certifications; got the CB certificate; complies with UL60950-1, IEC60950-1, EN60950-1, CAN/CSA C22.2 No. 60950 -1 |
Isolation | Input to output: 4242 Vdc; input to earth: 2121 Vdc; output to earth: 707 Vdc | |
EMC | EN55022 Class B, EN55024, EN61000-3-2, EN61000-3-3, ETSI EN300 386, ETSI EN301489, ITU-T K.20 | |
Lightening protection | Common model (input to earth) / differential model (input to input): 5KA (8/20uS, ITU-T K.44) |